Rigid polyurethane (PUR) pipe sections are low-temperature pipe insulation made from polyurethane foam. They have extremely low thermal conductivity and excellent insulating performance, and are often combined with high-density polyethylene (HDPE) jacket pipes to form prefabricated directly-buried insulated pipes. Product parameters are sourced from a commissioned inspection report by Hebei Quanhe Thermal Insulation Building Materials Co., Ltd. (Report No. J25D569348374BR, Shenzhen Jinglian Testing Co., Ltd., CNAS L18543, 2025-04-29). The tested sample (primary model Φ89×50×1000 mm) measured a thermal conductivity of 0.024 W/(m·K) at 25℃, density 46 kg/m³, compressive strength 197 kPa, oxygen index 30.5%, and closed-cell rate 85.5%. ⚠️ Important: PUR is a low-temperature insulation material suitable for long-term service temperatures not above 70℃ (the tested sample's operating points were 70℃/-30℃, with qualified dimensional-change rate). It is NOT suitable for high-temperature steam, furnaces, or other high-temperature duty, and must never be labeled as "high-temperature resistant." Please confirm the selection against your actual medium temperature. The test results are valid only for the sample tested.
| Density | 46 kg/m³ (measured on the tested sample; main tested model Φ89×50×1000 mm) |
| Material | Rigid polyurethane foam (PUR) |
| Size | Tested sample Φ89×50×1000 mm; the report also lists Φ76×40, Φ89×50, Φ159/219/377/426 × 50~80 and boards 1000×500×50 mm |
| Certification | Commissioned testing · CMA/CNAS (Shenzhen Jingli'an CNAS L18543, report No. J25D569348374BR) |
| Oxygen index | 30.5% (measured on the tested sample) |
| Closed-cell content | 85.5% (measured on the tested sample) |
| Service temperature | Suitable for continuous operating temperature ≤70°C (measured points 70°C / -30°C with acceptable dimensional change); PUR is a low-temperature material and must not be described as high-temperature resistant |
| Compressive strength | 197 kPa (measured on the tested sample) |
| Thermal conductivity | 0.024 W/(m·K) @25°C (measured on the tested sample, the lowest of the four pipe types; report J25D569348374BR) |
| Standard | GB/T 21558-2008, GB/T 50264-2013 |
| Fire rating |
Report No.:J25D569348374BR | Issuing Body:Shenzhen Jingli'an Testing Technology Co., Ltd.(CNAS L18543) | Issue Date:2025-04-29 | Commissioned testing
Tested Sample:Main tested size Φ89×50×1000 mm; test basis GB/T 21558-2008, GB/T 50264-2013 and the client's commissioning requirements
| Test Item | Measured Value | Standard Limit | Verdict |
|---|---|---|---|
| Thermal conductivity (25°C) | 0.024 W/(m·K) | ≤0.024 | Pass |
| Density | 46 kg/m³ | ≥35 | Pass |
| Compressive strength | 197 kPa | ≥180 | Pass |
| Tensile strength | 270 kPa | ≥200 | Pass |
| Oxygen index | 30.5 % | ≥30 | Pass |
| Closed-cell content | 85.5 % | ≤90 | Pass |
The tested sample (model Φ89×50×1000mm) measured 0.024 W/(m·K) @25℃, the lowest among the four pipe sections, per commissioned test report J25D569348374BR (Shenzhen Jinglian, CNAS L18543).
PUR is a low-temperature insulation material with a long-term service temperature not above 70℃ (tested point 70℃/-30℃, dimensional change qualified). It is NOT suitable for high-temperature steam or furnace duty, and must not be labeled "high-temperature resistant". Confirm by your actual medium temperature when selecting.
The tested sample measured compressive strength 197kPa, closed-cell rate 85.5%, and oxygen index 30.5%, all meeting relevant standards, indicating good structural strength and vapor-barrier performance.
The report lists Φ76×40, Φ89×50, Φ159/219/377/426×50~80 and board 1000×500×50mm etc., with the main tested size Φ89×50×1000mm; often combined with HDPE jacket pipe as prefabricated directly-buried insulation pipe. Contact sales for MOQ and lead time.
| Combustion performance of the tested sample was judged compliant under commissioned testing (see report J25D569348374BR for the exact class; it is not a Class A non-combustible material — note this when selecting) |
| Water absorption |
| 2.8 % |
| ≤3.0 |
| Pass |
| Water vapour transmission coefficient | 5.8 | ≤6.5 | Pass |
| pH value | 7.2 | 7.0~11.7 | Pass |
| Service temperature (dimensional change) | 70°C (0.51%) / -30°C (-0.27%) | — | Operating points measured in this report |